Nitrogen Gas Firefighting System

Nitrogen Gas Firefighting System

TECHNICAL SPECIFICATIONS

Fire extinction period from commencement of nitrogen injection 30 secs.(Max.)
Fire extinction period from activation of system 3 minutes (Max.)
Fire detector’s (quartz bulb) heat sensing temperature 141oC
Heat sensing area per detector Up to radius of 800 mm
Transformer Conservator Isolation valve setting 60 ltr / min (Minimum)
Capacity of nitrogen Generator 68 ltr (Minimum) with N2 storage tank for 10 m3 Nitrogen gas.
Power supply 230 VAC